Protective Relays
Relays that detect abnormal conditions and command breakers to trip — overcurrent, differential and distance protection.
Advanced
Modern numerical relays are microprocessor-based, combining many protection functions with communication (IEC 61850). Common functions (with ANSI codes):
- 50/51 Overcurrent — instantaneous and time-delayed (IDMT curves). Standard inverse IDMT: .
- 87 Differential — compares current entering and leaving a zone (transformers, generators, busbars); very selective.
- 21 Distance — measures impedance to the fault; zone 1 covers ~80 % of the line instantly, zone 2 and 3 with delays.
- 27/59 under/over-voltage, 81 frequency, 32 reverse power.
Selectivity is achieved by grading time and current settings so that the breaker nearest the fault trips first.