Whether generators stay in synchronism after disturbances — rotor angle, voltage and frequency stability.

Expert
Comments 0

The swing equation describes rotor dynamics:

2Hωsd2δdt2=Pm−PePe=EVXsin⁡δ\frac{2H}{\omega_s}\frac{d^2\delta}{dt^2} = P_m - P_e \qquad P_e = \frac{EV}{X}\sin\delta

  • Steady-state stability — small slow changes; maximum transferable power is EV/XEV/X.
  • Transient stability — large disturbances like faults; analysed with the equal area criterion: the system remains stable if the decelerating area can equal the accelerating area. Faster fault clearing increases the margin (critical clearing time).
  • Voltage stability and frequency stability — related to reactive power support and generation–load balance.

Grids defend stability with fast protection, excitation systems with PSS, automatic generation control and under-frequency load shedding.