Cable Sizing
Choose cable cross-section by current-carrying capacity, voltage drop and short-circuit withstand.
Intermediate
Three checks:
- Ampacity — the cable's rated current, after applying derating factors for ambient temperature, grouping and installation method, must exceed the design current, and the protective device rating must sit between them: .
- Voltage drop — single-phase: ; three-phase: . A common limit is about 3–5 % of nominal voltage.
- Short-circuit withstand — (adiabatic equation; ≈ 115 for PVC-insulated copper, 143 for XLPE copper).
Copper vs aluminium: aluminium is lighter and cheaper but needs about 1.6× the cross-section for the same resistance, and proper lugs to avoid loose, hot joints.