The change in secondary voltage from no load to full load, as a percentage of full-load voltage.

Intermediate
Comments 0

VR=Vnl−VflVfl×100%\text{VR} = \frac{V_{nl} - V_{fl}}{V_{fl}} \times 100\%

Approximate formula (per-unit values):

VR≈εrcos⁡ϕ±εxsin⁡ϕ\text{VR} \approx \varepsilon_r\cos\phi \pm \varepsilon_x\sin\phi

using + for lagging and − for leading power factor. A leading load can even produce negative regulation (the voltage rises with load). Distribution transformers use tap changers to keep the customer voltage within limits.