Transformer Equivalent Circuit
Model a real transformer with winding resistance, leakage reactance and a magnetising branch.
Advanced
The approximate equivalent circuit, referred to the primary:
- series winding resistance and leakage reactance , where ;
- a shunt magnetising branch: (core loss) in parallel with (magnetising current).
Parameters come from two tests:
- Open-circuit test (rated voltage, secondary open) → core loss and , .
- Short-circuit test (reduced voltage, rated current, secondary shorted) → copper loss and , .
The per-unit impedance (typically 4–10 % for distribution transformers) also sets the fault current a transformer can deliver.